PA link, consisting here of IM 153-2 High Feature Outdoor and DP/PA coupler
To create a smooth network transition between PROFIBUS DP and PROFIBUS PA, the SIMATIC product range offers two versions: the DP/PA coupler and the PA link.
The following criteria can be applied when choosing the network transition:
DP/PA coupler:
For small quantity frameworks (volumes of data) and low timing requirements; data transfer rate on the PROFIBUS DP limited to 45.45 Kbps
PA link:
For large number of nodes and high cycle time requirements; data transfer rate on the PROFIBUS DP up to 12 Mbps
The two PA gateways are based on two versions of the DP/PA coupler:
Ex [i] DP/PA coupler (max. output current 110 mA)
For implementation of PROFIBUS PA networks with a line or tree topology in environments up to Ex Zone 1/21; not for redundant architectures (coupler redundancy, ring)
DP/PA coupler FDC 157-0 (max. output current 1 000 mA)
For implementation of PROFIBUS PA networks with a line, tree or ring topology in environments up to Ex Zone 2/22; can be used for the "Ring" and "Line with coupler redundancy" redundant architectures.
DP/PA couplers are also integral components of the PA link (see design). The PA link connects PROFIBUS DP and PROFIBUS PA together, and decouples the transmission rates. In contrast to the DP/PA coupler gateway which limits the data transmission rate on the PROFIBUS DP to 45.45 Kbps, the PA link does not influence the performance of the PROFIBUS DP.
The PA link functions as a slave on the PROFIBUS DP and as a master on the PROFIBUS PA. From the viewpoint of the host PROFIBUS DP master, the PA link is a modular slave whose modules are the devices connected on the PROFIBUS PA. Addressing of these devices is carried out indirectly via the PA link that itself only requires one node address. The host PROFIBUS master can scan devices connected to the PA link all at once.
If the gateway is a DP/PA coupler, the nodes on the PROFIBUS PA are directly addressed by the PROFIBUS DP master (controller). The DP/PA coupler is an electrical node, but is transparent for communication between the master and PA field devices; it therefore does not require setting of parameters or addresses (exception: FDC 157-0 DP/PA coupler used as PROFIBUS diagnostics slave).
FDC 157-0 DP/PA couplers configured as PROFIBUS diagnostics slaves supply extensive diagnostic and status information via PROFIBUS for swift localization and correction of faults:
I&M (identification & maintenance) data
Current and voltage values on the main line
Redundancy status
Wire break
Short-circuit
Signal level
To this end, each of these DP/PA couplers FDC 157‑0 requires its own PROFIBUS address. This applies independent of use in a PA link or as a PA gateway.
The PA link and DP/PA coupler are available for use in operating environments up to Ex Zone 2/22. Both are operated with 24 V DC. Assembly is on an S7-300 mounting rail with horizontal or vertical alignment.
Configuration examples for PA link and DP/PA coupler
The PA link is a modular combination in S7-300 design consisting of the IM 153‑2 High Feature Outdoor PROFIBUS DP interface module (with optional redundancy) and up to 5 DP/PA couplers (FDC 157‑0 or Ex [i]).
All components of the PA link are interconnected through the S7 backplane bus. Use of active bus modules on the backplane allows hot swapping of individual modules and redundancy of the IM 153‑2 High Feature Outdoor PROFIBUS DP interface modules and the FDC 157‑0 DP/PA couplers. If redundancy and changes during operation are not required, passive bus connectors can be used instead of active bus modules.
The PS 307 or PS 305 load power supply can be used for the 24 V DC. With a redundant IM 153-2 High Feature Outdoor PROFIBUS DP interface module, a redundant 24 V DC supply is also recommended, e.g. using two PS 307/PS 305 load current supplies.
The PROFIBUS PA bus segments designed with the DP/PA couplers are physically separated as regards current infeed, but form one bus system in communication terms. A PROFIBUS PA ring segment or a PROFIBUS PA line segment with coupler redundancy can be operated on a PA link. Further PROFIBUS PA line segments can be operated on this PA link using individual couplers. The FDC 157‑0 DP/PA couplers provided for the ring coupling or coupler redundancy must always be located at the right-hand end of a sequence of up to 5 couplers.
The following basic components are available for configuring the PA link:
IM 153‑2 High Feature Outdoor interface
DP/PA coupler (Ex [i] and FDC 157‑0)
Components for redundant design and for hot swapping:
Mounting rail for hot swapping (as an alternative to the standard mounting rail)
BM PS/IM for 1 load power supply and 1 IM 153‑2 High Feature Outdoor module
BM IM/IM for 2 IM 153-2 High Feature Outdoor modules, for redundant and non-redundant configuration
BM FDC for 1 DP/PA coupler Ex [i] or FDC 157-0 (up to 5 DP/PA couplers possible per PA link)
BM FDC/FDC for 2 DP/PA couplers FDC 157-0
Additive options:
PS 307 for 120/230 V AC; 24 V DC load power supply, version in 2, 5 or 10 A, or
PS 305 load power supply for 24/48/60/110 V DC; 24 V DC, 2 A
DP/PA Coupler | |
Bus connection | |
Connection for PROFIBUS PA | |
DP/PA coupler Ex [i] | 2 terminals of a 4‑pin screw-type terminal, integrated terminating resistor |
DP/PA coupler FDC 157-0 | 4‑pin screw-type terminal for connection and looping through, selectable terminating resistor |
Connection for PROFIBUS DP | 9‑pin D-sub connector |
Module-specific data | |
Degree of protection | IP20 |
Transmission rate | |
On PROFIBUS DP | 45.45 Kbps |
On PROFIBUS PA | 31.25 Kbps |
Communication protocol | PROFIBUS DP |
Voltages, currents, potentials | |
Supply voltage | 24 V DC (20.4 … 28.8 V) |
Reverse polarity protection | Yes |
Overvoltage protection | Yes |
Voltage at coupler output (PA) | |
DP/PA coupler Ex [i] | 13 … 14 V DC |
DP/PA coupler FDC 157-0 | 31 ± 1 V DC |
Voltage monitoring | 15.5 V |
Overvoltage monitoring | U > 35 V; latching cutoff |
Voltage failure bridging | Min. 5 ms |
Current at coupler output (PA) | |
DP/PA coupler Ex [i] | Max. 110 mA |
DP/PA coupler FDC 157-0 | Max. 1 A |
Galvanic isolation 24 V DC | |
PROFIBUS DP/PROFIBUS PA | Yes |
PROFIBUS DP/supply | Yes |
PROFIBUS PA/supply | Yes |
All electric circuits/functional grounding | Yes |
Power consumption of modules (24 V DC) | |
DP/PA coupler Ex [i] | Max. 400 mA |
DP/PA coupler FDC 157-0 | Max. 2.3 A |
Module power loss | |
DP/PA coupler Ex [i] | Typ. 7 W |
DP/PA coupler FDC 157-0 | Typ. 13.4 W |
Status, interrupts, diagnostics | |
Diagnostics displays DP/PA coupler Ex [i] and DP/PA coupler FDC 157‑0 | |
PROFIBUS DP bus monitoring | Yellow "DP" LED |
PROFIBUS PA bus monitoring | Yellow "PA" LED |
24 V DC power supply monitoring | Green "ON" LED |
Additive diagnostics displays of the DP/PA coupler FDC 157‑0 | |
Group error | Red LED "SF" |
Bus error | Red LED "BF" |
Monitoring DP/PA coupler (active coupler in redundant configuration) | Yellow "ACT" LED |
Climatic conditions | |
Permissible operating temperature | |
Horizontal installation | -25 to +60 °C |
Vertical installation | -25 to +40 °C |
Dimensions and weight | |
Dimensions (W × H × D) in mm | 80 × 125 × 130 |
Weight | |
DP/PA coupler Ex [i] | Approx. 550 g |
DP/PA coupler FDC 157-0 | Approx. 515 g |
IM 153-2 High Feature Outdoor | |
Bus connection | |
Connection for PROFIBUS DP | 9‑pin D-sub connector, contact assignment as described in IEC 61158/EN 50170, Vol. 2 |
Connectable lower-level components | |
Number of couplers | |
DP/PA coupler | Max. 5 |
Y coupler | 1 |
Number of PA devices on PROFIBUS PA | Max. 64 |
Module-specific data | |
Degree of protection | IP20 |
Transmission rate of the higher level DP master system | 9.6; 19.2; 45.45; 93.75; 187.5; 500 Kbps |
Communication protocol | PROFIBUS DP |
Frame length | |
I/O data | Max. 244 bytes |
Configuration frame | Max. 244 bytes |
Diagnostics frame | Max. 244 bytes |
Parameter assignment frame | Max. 244 bytes |
Voltages, currents, potentials | |
Supply voltage | 24 V DC (20.4 … 28.8 V) |
Reverse polarity protection | Yes |
Voltage failure bridging | 20 ms |
Galvanic isolation | |
To the higher-level DP master system | Yes |
To the DP/PA coupler or Y coupler | No |
Power consumption of modules (24 V DC) | |
In the PA link | Max. 200 mA (at 20.4 V) |
In the Y link | Max. 400 mA (at 20.4 V) |
Module power loss | |
In the PA link | Max. 2.6 W (at 28.8 V) |
In the Y link | Max. 3.6 W (at 28.8 V) |
Infeed, mechanical design | 4‑pin screw terminal, short-circuiting link between PE and M24; the short-circuiting link must be removed for floating operation (independent of this, the DP interface is always floating) |
Status, interrupts, diagnostics | |
Diagnostic displays | |
Group error | Red LED "SF" |
Bus error on higher level DP master system | Red LED "BF 1" |
Bus error on underlying bus system | Red LED "BF 2" |
Module is active in redundancy mode | Yellow "ACT" LED |
24 V DC power supply monitoring | Green "ON" LED |
Climatic conditions | |
Permissible operating temperature | |
Horizontal installation | -25 to +60 °C |
Vertical installation | -25 to +40 °C |
Dimensions and weight | |
Dimensions (W × H × D) in mm | 40 × 125 × 130 |
Weight | Approx. 360 g |
列表价(不含税) | 显示价格 | |
您的单价(不含税) | 显示价格 | |
服务和支持 (手册,,问答...) | 下载 | |
该产品的培训课程 | SITRAIN – 数字化工业学院 |
产品 | ||||||||||||||||||||||||||||||||||
商品编号(市售编号) | 6ES7153-2BA70-0XB0 | |||||||||||||||||||||||||||||||||
产品说明 | SIMATIC DP,接口连接 DP/PA LINK 和 ET200M IM153-2 HF 用于扩展温度范围 针对多 12 个 S7-300 模块 具有冗余能力, 时间戳 适合时钟同步运行 新特性: 直至多 12 个模块可使用 从站主动发起针对 Drive ES(驱动工程软件) 和 Switch ES(交换机工程软件) 扩展的组态范围 针对 HART 协议的辅助变量 64 通道模块的运行 32 个信号/插槽 +++ 遵守手册中的 兼容性提示+++ | |||||||||||||||||||||||||||||||||
产品家族 | IM 153-1/153-2 | |||||||||||||||||||||||||||||||||
产品生命周期 (PLM) | PM300:有效产品 | |||||||||||||||||||||||||||||||||
价格数据 | ||||||||||||||||||||||||||||||||||
价格组 / 总部价格组 | BD / 280 | |||||||||||||||||||||||||||||||||
列表价(不含税) | 显示价格 | |||||||||||||||||||||||||||||||||
您的单价(不含税) | 显示价格 | |||||||||||||||||||||||||||||||||
金属系数 | 无 | |||||||||||||||||||||||||||||||||
交付信息 | ||||||||||||||||||||||||||||||||||
出口管制规定 | AL : N / ECCN : EAR99H | |||||||||||||||||||||||||||||||||
工厂生产时间 | 195 天 | |||||||||||||||||||||||||||||||||
净重 (Kg) | 0.288 Kg | |||||||||||||||||||||||||||||||||
包装尺寸 | 12.90 x 15.20 x 5.10 | |||||||||||||||||||||||||||||||||
包装尺寸单位的测量 | CM | |||||||||||||||||||||||||||||||||
数量单位 | 1 件 | |||||||||||||||||||||||||||||||||
包装数量 | 1 | |||||||||||||||||||||||||||||||||
其他产品信息 | ||||||||||||||||||||||||||||||||||
EAN | 4047623404217 | |||||||||||||||||||||||||||||||||
UPC | 804766132315 | |||||||||||||||||||||||||||||||||
商品代码 | 85389091 | |||||||||||||||||||||||||||||||||
LKZ_FDB/ CatalogID | STPCS7 | |||||||||||||||||||||||||||||||||
产品组 | 2488 | |||||||||||||||||||||||||||||||||
组代码 | R336 | |||||||||||||||||||||||||||||||||
原产地 | 德国 | |||||||||||||||||||||||||||||||||
Compliance with the substance restrictions according to RoHS directive | RoHS 合规开始日期: 2014.05.12 | |||||||||||||||||||||||||||||||||
产品类别 | A: 问题无关,即刻重复使用 | |||||||||||||||||||||||||||||||||
电气和电子设备使用后的收回义务类别 | - | |||||||||||||||||||||||||||||||||
REACH Art. 33 责任信息 | ||||||||||||||||||||||||||||||||||
分类 | ||||||||||||||||||||||||||||||||||
|
西门子RS485 DP总线电缆 西门子RS485 DP总线电缆