    SIMATIC PCS neo offers the possibility to monitor and control the sequential control systems configured in engineering without additional configuration work. In the operation and the selection of additional information, SFC visualization follows the concept of APL faceplates.

    SFC faceplate

    Entire sequencers can be displayed in a detail view and the processing of steps and transitions can be tracked. Details of the steps and transitions are displayed in a separate window and the current values of the logic operations in the transitions and steps are shown dynamically in a separate view.

    SFC

    In the SIMATIC PCS neo process control system, various communication protocols that enable connection of external components or systems are available to the user on the server (M&C). The following protocols are supported.

    OPC UA server

    OPC UA client

    Support of further protocols will be provided in future versions of SIMATIC PCS neo. 

    For connection to an S7-410 CPU, the following protocols in the form of a block library are supported:

    Modbus TCP master

    Modbus TCP slave

    COM library

    OPC UA

    OPC UA will be available in SIMATIC PCS neo as both a client and a server version.

    OPC UA server

    As OPC UA server, the SIMATIC PCS neo process control system can be integrated directly into higher-level systems for production planning and process data evaluation and management. These higher-level systems (OPC UA clients) can access SIMATIC PCS neo process data or alarms and messages via the OPC UA server.

    The connection is secured by means of authorization and encryption. Access of an OPC UA client to data in PCS neo is subject to the same user roles and rights verifications as an operator of the M&C.

    The OPC UA server configured on an M&C server can access data of all M&C servers in a PCS neo system. Multiple OPC UA servers are also possible.

    OPC UA client

    With OPC UA, lower-level systems can be integrated directly into the SIMATIC PCS neo process control system as an OPC UA server. These lower-level systems can write to the data management via the OPC UA client in the M&C server and/or receive data from the M&C server via the OPC UA client.

    It is therefore possible to integrate devices that support OPC UA into SIMATIC PCS neo with an "Operator Control & Monitoring" functionality.

    Modbus TCP

    SIMATIC PCS neo is supplied with a Modbus TCP block library for the SIMATIC S7-410 CPU as standard. This library offers the possibility with various CFC blocks to both receive data in the CPU and make data available from the CPU to a higher-level device or system.

    To use the Modbus TCP library, a license is needed for every automation system in which the library is used.

    Serial Modbus devices with Modbus RTU that are connected to the CPU via serial / TCP converters can also be connected using Modbus TCP blocks. Configuration of the serial/TCP converter takes place outside of SIMATIC PCS neo.

    Conversion of the Modbus RTU frame into a Modbus TCP frame is supported by the block library.

    Modbus TCP master

    The Modbus TCP master functionality in the SIMATIC S7-410 CPU provides the possibility to integrate lower-level devices or systems into the SIMATIC PCS neo process control system via the Modbus protocol.

    The Modbus **s from the lower-level devices or systems can be used for further processing in the CPU or displayed in SIMATIC PCS neo M&C.

    Modbus TCP slave

    The Modbus TCP slave functionality in the SIMATIC S7-410 CPU offers the possibility to make values available to higher-level devices or systems. Note that the process values are forwarded directly from the CPU in this case.

    COM library

    The COM library in PCS neo consists of a TCP communication library and an S7 Put/Get library. Both libraries are CFC-based block libraries for the SIMATIC S7-410 CPU that allow for the exchange of values between various SIMATIC CPUs.

    功能

    OPC UA server

    The OPC UA interface is based on various OPC UA specifications; see the relevant standard for details. In addition to the DA (Data Access) information model, the SIMATIC PCS neo OPC UA server also supports AC (Alarms & Conditions) and thus makes current data from the SIMATIC PCS neo M&C data management available to other applications. Other information models and functions will be considered in future SIMATIC PCS neo versions.

    The OPC UA client can log itself on to ongoing changes or also write values. Access takes place via a flat list. Access via additional information models will be considered in future SIMATIC PCS neo versions.

    The connection to the OPC UA client is secured by means of authorization and encryption. Access of an OPC UA client to data in PCS neo is subject to the same user roles and rights verifications as an operator of the M&C.

    The OPC UA server configured on an M&C server can access data of all M&C servers in a PCS neo system. Multiple OPC UA servers are also possible.

    OPC UA client

    The OPC UA interface is based on various OPC UA specifications; see the relevant standard for details. The SIMATIC PCS neo OPC UA client supports the DA (data access) information model and can thus write current data to the SIMATIC PCS neo M&C data management and receive commands from the data management. Other information models and functions will be considered in future SIMATIC PCS neo versions.

    Access takes place via a flat list. Access via a data model will be considered in future SIMATIC PCS neo versions.

    Modbus TCP master

    The Modbus TCP master library contains the following blocks:

    MODBUS_TCP_CLIENT (configuration block)

    MODBUS_DI16 (management of up to 16 digital inputs)

    MODBUS_DO16 (management of up to 16 digital outputs)

    MODBUS_AI1 (management of an input analog value)

    MODBUS_AO1 (management of an output analog value)

    MODBUS_INT_AI16 (management of up to 16 integer inputs)

    MODBUS_INT_AO16 (management of up to 16 integer outputs)

    MODBUS_AI_EXT (extension of the input analog value to reduce the number of requests with the same volume of data)

    MODBUS_AI16_EXT (extension of the input analog value by up to 16 analog inputs to reduce the number of requests with the same volume of data)

    MODBUS_AO16_EXT (extension of the output analog value by up to 16 analog outputs to reduce the number of requests with the same volume of data)

    MODBUS_AO_EXT (extension of the output analog value to reduce the number of requests with the same volume of data)

    MODBUS_DO32_EXT (extension of the output analog value to reduce the number of requests with the same volume of data)

    MODBUS_DI32_EXT (extension of the output analog value to reduce the number of requests with the same volume of data)

    Modbus TCP slave

    The Modbus TCP slave library contains the following blocks:

    MODBUS_TCP_SERVER (configuration block)

    MODBUS_DI16 (management of up to 16 digital inputs)

    MODBUS_DO16 (management of up to 16 digital outputs)

    MODBUS_AI1 (management of an input analog value)

    MODBUS_AO1 (management of an output analog value)

    COM library

    The COM library contains the following blocks:

    TCPCon (configuration block for single connections)
    Note: As of PCS neo V3.1, this block will be replaced with the block TCPConR.

    TCPConR (configuration block for single and redundant connections)

    S7Con (configuration block of a configured S7 Put/Get connection)

    Rcv_AnaVal (management of up to 8 analog inputs)

    Rcv_DigVal (management of up to 8 digital inputs)

    RcvH_AnaVal (management of up to 8 analog inputs using a redundant connection)
    Note: This block is no longer needed as of PCS neo V3.1. The redundancy capability is realized with the configuration block TCPConR.

    RcvH_DigVal (management of up to 8 digital inputs using a redundant connection)
    Note: This block is no longer needed as of PCS neo V3.1. The redundancy capability is realized with the configuration block TCPConR.

    Snd_AnaVal (management of up to 8 analog outputs)

    Snd_DigVal (management of up to 8 digital outputs)

    SndH_AnaVal (management of up to 8 analog outputs using a redundant connection)
    Note: This block is no longer needed as of PCS neo V3.1. The redundancy capability is realized with the configuration block TCPConR.

    SndH_DigVal (management of up to 8 digital outputs using a redundant connection)
    Note: This block is no longer needed as of PCS neo V3.1. The redundancy capability is realized with the configuration block TCPConR.

    S7Get (configuration block to receive data from an external device)

    S7Put (configuration block to send data to an external device)



    http://yan6789.b2b168.com
    欢迎来到浔之漫智控技术(上海)有限公司网站, 具体地址是上海市松江区小昆山镇 广富林4588弄52号3楼,联系人是颜经理。 主要经营浔之漫智控技术(上海)有限公司负责西门子低压电器授权代理商、西门子模块总代理商、西门子中国一级代理商、西门子PLC模块总代理商、西门子PLC一级代理商、西门子DP电缆代理商,本公司专销售西门子各系列产品;西门子保内全新产品质保一年。一年内因产品质量问题*换新产品;不收取任何费。 。 单位注册资金单位注册资金人民币 100 万元以下。 价格战,是很多行业都有过的恶性竞争,不少厂家为了在价格战役中获胜,不惜以牺牲产品质量为代价,而我们公司坚决杜绝价格战,坚持用优质的原材料及先进的技术确保产品质量,确保消费者的合法利益。