电源电压 3 AC 500 ... 690 V | 逆变装置 | ||||||
---|---|---|---|---|---|---|---|
| 6SL3325-1TG31-0AA3 | 6SL3325-1TG31-5AA3 | 6SL3325-1TG32-2AA3 | 6SL3325-1TG33-3AA3 | 6SL3325-1TG34-7AA3 | 6SL3325-1TG35-8AA3 | |
类型等级 |
|
|
|
|
|
|
|
I L (50 Hz 690 V) 时1) | kW | 90 | 132 | 200 | 315 | 450 | 560 |
I H (50 Hz 690 V) 时1) | kW | 75 | 110 | 160 | 250 | 400 | 450 |
I L (50 Hz 500 V) 时1) | kW | 55 | 90 | 132 | 200 | 315 | 400 |
I H (50 Hz 500 V) 时1) | kW | 55 | 90 | 132 | 200 | 250 | 315 |
I L (60 Hz 575 V) 时2) | [hp] | 75 | 150 | 200 | 300 | 450 | 600 |
I H (60 Hz 575 V) 时2) | [hp] | 75 | 125 | 200 | 250 | 450 | 500 |
输出电流 |
|
|
|
|
|
|
|
额定电流 Irated O | A | 100 | 150 | 215 | 330 | 465 | 575 |
基本负载电流 IL3) | A | 95 | 142 | 208 | 320 | 452 | 560 |
基本负载电流 IH4) | A | 89 | 134 | 192 | 280 | 416 | 514 |
大电流 Imax O | A | 142 | 213 | 312 | 480 | 678 | 840 |
直流环节电流 |
|
|
|
|
|
|
|
额定电流 Irated DC |
|
|
|
|
|
|
|
基本整流装置 | A | 122 | 183 | 263 | 403 | 558 | 702 |
有源整流装置 | A | 110 | 165 | 237 | 363 | 502 | 632 |
基准负载电流 IL DC3) |
|
|
|
|
|
|
|
基本整流装置 | A | 116 | 173 | 253 | 390 | 544 | 683 |
有源整流装置 | A | 105 | 156 | 229 | 352 | 489 | 616 |
基准负载电流 IH DC 4) |
|
|
|
|
|
|
|
基本整流装置 | A | 108 | 163 | 234 | 341 | 496 | 627 |
有源整流装置 | A | 98 | 147 | 211 | 308 | 446 | 565 |
电流要求 |
|
|
|
|
|
|
|
24 V DC 辅助电源 | A | 1.0 | 1.0 | 1.5 | 1.5 | 1.6 | 1.6 |
直流环节电容 | μF | 2800 | 2800 | 4200 | 5800 | 9670 | 9670 |
脉冲频率 5) |
|
|
|
|
|
|
|
额定频率 | kHz | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 |
脉冲频率,大值 |
|
|
|
|
|
|
|
*电流降额 | kHz | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 |
有电流降额 | kHz | 7.5 | 7.5 | 7.5 | 7.5 | 7.5 | 7.5 |
大功耗 6) |
|
|
|
|
|
|
|
50 Hz 690 V 时 | kW | 1.15 | 1.64 | 2.34 | 3.38 | 5.44 | 5.61 |
60 Hz 575 V 时 | kW | 1.02 | 1.45 | 2.05 | 2.96 | 5.1 | 5.45 |
散热到周围空气 | kW | 0.06 | 0.07 | 0.09 | 0.12 | 0.14 | 0.16 |
冷却液体积流量 7) | 升/分钟(美国加仑/分钟) | 9 (2.38) | 9 (2.38) | 12 (3.17) | 12 (3.17) | 16 (4.23) | 16 (4.23) |
液体流量 集成换热器中 | dm3 | 0.31 | 0.31 | 0.91 | 0.91 | 0.74 | 0.74 |
压降,典型8) 体积流量 | [Pa] | 70000 | 70000 | 70000 | 70000 | 70000 | 70000 |
换热器材质 |
| 不锈钢 | 不锈钢 | 不锈钢 | 不锈钢 | 铝 | 铝 |
冷却液连接 浸液管/回流管 | 管螺纹 ISO 228 G 3/4 B | ||||||
噪声等级 LpA (1 m),50/60 Hz | dB | 52 | 52 | 52 | 52 | 54 | 54 |
直流环节接口 DCP, DCN |
| 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 |
电机连接 U2, V2, W2 |
| M12 孔 | M12 孔 | M12 孔 | M12 孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 |
大导线截面积 (IEC) | mm2 | 2 × 95 | 2 × 95 | 4 × 240 | 4 × 240 | 4 × 185 | 4 × 185 |
PE/GND 连接 |
| 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 |
大导线截面积 (IEC) | mm2 | 2 × 95 | 2 × 95 | 2 × 240 | 2 × 240 | 4 × 185 | 4 × 185 |
大电缆长度 9) |
|
|
|
|
|
|
|
屏蔽 | m (ft) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) |
非屏蔽 | m (ft) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) |
外形尺寸 |
|
|
|
|
|
|
|
宽度 | mm (in) | 150 (5.91) | 150 (5.91) | 150 (5.91) | 150 (5.91) | 265 (10.4) | 265 (10.4) |
高 | mm (in) | 728 (28.7) | 728 (28.7) | 1172 (46.1) | 1172 (46.1) | 1002 (39.4) | 1002 (39.4) |
深度 | mm (in) | 545 (21.5) | 545 (21.5) | 545 (21.5) | 545 (21.5) | 545 (21.5) | 545 (21.5) |
重量,约 | kg (lb) | 41 (90.4) | 41 (90.4) | 80 (176) | 80 (176) | 110 (243) | 110 (243) |
框架型号 |
| FXL | FXL | GXL | GXL | HXL | HXL |
1) 典型 6 较标准感应电机的额定功率,基于 IL 或 IH,电源 500 V 或 690 V 3 AC 50 Hz。
2)典型 6 较标准感应电机的额定功率,基于 IL 或 IH,电源 575 V 3 AC 60 Hz。
3) 基本负载电流IL 基于 110% 的负荷循环 (60 s) 或 150% 的负荷循环 (10 s),负荷周期为 300 s。
4) 基本负载电流IH 基于 150% 的负荷循环 (60 s) 或 160% 的负荷循环 (10 s),负荷周期为 300 s。
5) 关于脉冲频率和大输出电流/ 输出频率之间的相互关系,请参见《SINAMICS 低压工程手册》。
6) 标定的功耗是在 ** 负载时的大值。正常情况下,损耗相应会低些。为了将少量能量损耗安全散发到环境空气中,请遵循《SINAMICS 低压工程手册》中有关控制柜安装的说明。
7) 该值适用于含水冷却液以及水和防冻剂的混合液。
8) 该值适用于作为冷却液的水。《SINAMICS 低压工程组态手册》中提供了有关其它冷却液的附加信息和说明。
9) 所有电机电缆和直流环节。长电缆的特殊配置请咨询西门子公司。有关详细资料,请参见《SINAMICS 低压工程手册》。
电源电压 3 AC 500 ... 690 V | 逆变装置 | ||||||
---|---|---|---|---|---|---|---|
| 6SL3325-1TG37-4AA3 | 6SL3325-1TG38-0AA3 1) | 6SL3325-1TG38-1AA3 | 6SL3325-1TG41-0AA3 | 6SL3325-1TG41-3AA3 | 6SL3325-1TG41-6AP3 11) | |
类型等级 |
|
|
|
|
|
|
|
I L (50 Hz 690 V) 时2) | kW | 710 | 800 | 800 | 1000 | 1200 | 1500 |
I H (50 Hz 690 V) 时2) | kW | 630 | 710 | 710 | 900 | 1000 | 1260 |
I L (50 Hz 500 V) 时2) | kW | 500 | 560 | 560 | 710 | 900 | 1000 |
I H (50 Hz 500 V) 时2) | kW | 450 | 500 | 560 | 630 | 800 | 900 |
I L (60 Hz 575 V) 时3) | [hp] | 700 | 800 | 800 | 1000 | 1250 | 1500 |
I H (60 Hz 575 V) 时3) | [hp] | 700 | 700 | 700 | 900 | 1000 | 1250 |
输出电流 |
|
|
|
|
|
|
|
额定电流 Irated O | A | 735 | 810 | 810 | 1025 | 1270 | 1560 |
基本负载电流 IL4) | A | 710 | 790 | 790 | 1000 | 1230 | 1500 |
基本负载电流 IH 5) | A | 657 | 724 | 724 | 917 | 1136 | 1370 |
大电流 Imax O | A | 1065 | 1185 | 1185 | 1500 | 1845 | 2250 |
直流环节电流 |
|
|
|
|
|
|
|
额定电流 Irated DC |
|
|
|
|
|
|
|
基本整流装置 | A | 903 | 990 | 990 | 1250 | 1550 | 1903 |
有源整流装置 | A | 808 | 891 | 891 | 1125 | 1395 | 1714 |
基准负载电流 IL DC4) |
|
|
|
|
|
|
|
基本整流装置 | A | 870 | 948 | 963 | 1219 | 1500 | 1800 |
有源整流装置 | A | 781 | 870 | 869 | 1100 | 1353 | 1650 |
基准负载电流 IH DC 5) |
|
|
|
|
|
|
|
基本整流装置 | A | 795 | 885 | 883 | 1118 | 1384 | 1680 |
有源整流装置 | A | 732 | 808 | 796 | 1009 | 1250 | 1550 |
电流要求 |
|
|
|
|
|
|
|
24 V DC 辅助电源 | A | 1.6 | 1.6 | 1.46 | 1.46 | 1.46 | 1.46 |
直流环节电容 | μF | 10500 | 10500 | 14000 | 16000 | 19330 | 21000 |
脉冲频率 6) |
|
|
|
|
|
|
|
额定频率 | kHz | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 |
脉冲频率,大值 |
|
|
|
|
|
|
|
*电流降额 | kHz | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 |
有电流降额 | kHz | 7.5 | 7.5 | 7.5 | 7.5 | 7.5 | 7.5 |
大功耗 6) |
|
|
|
|
|
|
|
50 Hz 690 V 时 | kW | 7.65 | 8.47 | 9.56 | 10.87 | 13.49 | 17.9 |
60 Hz 575 V 时 | kW | 6.67 | 7.39 | 8.34 | 9.55 | 11.84 | 15.7 |
散热到周围空气 | kW | 0.2 | 0.22 | 0.43 | 0.53 | 0.57 | 0.78 |
冷却液体积流量 8) | 升/分钟(美国加仑/分钟) | 16 (4.23) | 16 (4.23) | 27 (7.13) | 27 (7.13) | 27 (7.13) | 27 (7.13) |
液体流量 集成换热器中 | dm3 | 0.74 | 0.74 | 1.56 | 1.56 | 1.56 | 1.56 |
压降,典型9) 体积流量 | [Pa] | 70000 | 70000 | 70000 | 70000 | 70000 | 70000 |
换热器材质 |
| 铝 | 铝 | 铝 | 铝 | 铝 | 铝 |
冷却液连接 浸液管/回流管 | 管螺纹 ISO 228 G 3/4 B | ||||||
噪声等级 LpA (1 m),50/60 Hz | dB | 54 | 54 | 56 | 56 | 56 | 56 |
直流环节接口 DCP, DCN |
| 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 | 2 个 M12 螺孔 母线 |
电机连接 U2, V2, W2 |
| 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 |
大导线截面积 (IEC) | mm2 | 4 × 185 | 4 x 185 | 母线 | 母线 | 母线 | 母线 |
PE/GND 连接 |
| 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 | 2 个 M12 螺孔 |
大导线截面积 (IEC) | mm2 | 4 × 185 | 4 × 185 | 母线 | 母线 | 母线 | 母线 |
电缆长度,大值 10) |
|
|
|
|
|
|
|
屏蔽 | m (ft) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) |
非屏蔽 | m (ft) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) |
外形尺寸 |
|
|
|
|
|
|
|
宽度 | mm (in) | 265 (10.4) | 265 (10.4) | 295 (11.6) | 295 (11.6) | 295 (11.6) | 295 (11.6) |
高 | mm (in) | 1002 (39.4) | 1002 (39.4) | 1516 (59.7) | 1516 (59.7) | 1516 (59.7) | 1516 (59.7) |
深度 | mm (in) | 545 (21.5) | 545 (21.5) | 545 (21.5) | 545 (21.5) | 545 (21.5) | 545 (21.5) |
重量,约 | kg (lb) | 110 (243) | 110 (243) | 220 (485) | 220 (485) | 220 (485) | 230 (507) |
框架型号 |
| HXL | HXL | JXL | JXL | JXL | JXL |
1) 此装置针对 1.25 kHz 的基本脉冲频率进行了优化;对于增加的脉冲频率 - 或对于某些过载,降额因数**订货号为6SL3325-1TG38-1AAx的器件的降额因数。
2) 典型 6 较标准感应电机的额定功率,基于 IL 或 IH,电源 500 V 或 690 V 3 AC 50 Hz。
3)典型 6 较标准感应电机的额定功率,基于 IL 或 IH,电源 575 V 3 AC 60 Hz。
4) 基本负载电流IL 基于 110% 的负荷循环 (60 s) 或 150% 的负荷循环 (10 s),负荷周期为 300 s。
5) 基本负载电流IH 基于 150% 的负荷循环 (60 s) 或 160% 的负荷循环 (10 s),负荷周期为 300 s。
6) 关于脉冲频率和大输出电流/ 输出频率之间的相互关系,请参见《SINAMICS 低压工程手册》。
7) 标定的功耗是在 ** 负载时的大值。正常情况下,损耗相应会低些。为了将少量能量损耗安全散发到环境空气中,请遵循《SINAMICS 低压工程手册》中有关控制柜安装的说明。
8) 该值适用于含水冷却液以及水和防冻剂的混合液。
9) 该值适用于作为冷却液的水。《SINAMICS 低压工程组态手册》中提供了有关其它冷却液的附加信息和说明。
10) 所有电机电缆和直流环节。长电缆的特殊配置请咨询西门子公司。有关详细资料,请参见《SINAMICS 低压工程手册》。
11)适用于 5 Hz 到 10 Hz 输出频率的附加负载率:基本负载电流 = 1460 A,短时电流 = 2340 A,时间 5 s,负载持续时间 600 s。对于 1 Hz 到 5 Hz 输出频率,短时电流为 1900 A,时间 5 s。