西门子5SY4CV高分断型工业微断授权代理商
西门子5SY4CV高分断型工业微断授权代理商
6AT8007-1AA10-0AA0 SIPLUS CMS1200 SM1281 状态监控,用于 SIMATIC S7-1200 4 个 IEPE 振动通道 1 个数字输入端,用于 转速采集 |
SIPLUS CMS1200 SM 1281 Condition Monitoring forms part of SIMATIC S7-1200 and is used for the:
Monitoring of motors, generators, pumps, fans, or other mechanical components
Recording and analysis of vibrations
Expansion capability of up to 7 modules
SIPLUS CMS1200 SM 1281 Condition Monitoring includes:
Integrated diagnostics software
4 IEPE interfaces for vibration sensors
1 speed input
The following accessories can also be ordered, see "Accessories":
SIPLUS CMS1200 SM 1281 shield clamp set for EMC-compliant cable connection
VIB-SENSOR vibration sensor for recording vibrations
CABLE-MIL connecting cable, several cable length available
SIPLUS CMS1200 SM 1281 Condition Monitoring comes with the following fixed functional scope as standard:
Characteristic values (bearing, vibration monitoring)
Frequency-selective analysis using FFT, H‑FFT
Trend analysis
Limit value monitoring of frequency bands
Recording with time stamp of trend values, raw data, frequency spectra, alarm log
Simple localization of damage using fingerprint comparison
Output of system and status messages
Extraction of raw data for further diagnoses
Web server
Article number | 6AT8007-1AA10-0AA0 | |
---|---|---|
SM1281_Condition_Monitoring | ||
General information |
| |
Product type designation | SM1281 | |
Product description | S7-1200 module for the monitoring of vibrations on mechanical components based on parameters and frequency-selective analysis functions | |
Installation type/mounting |
| |
Mounting type | Rail or wall mounting | |
Mounting position | Horizontal, vertical | |
Recommended mounting position | Horizontal | |
Supply voltage |
| |
Type of supply voltage | DC | |
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current |
| |
Current consumption, typ. | 200 mA | |
Current consumption, max. | 250 mA | |
from backplane bus 5 V DC, typ. | 80 mA | |
from backplane bus 5 V DC, max. | 85 mA | |
Power loss |
| |
Power loss, typ. | 4.8 W | |
Memory |
| |
Total memory capacity | 1 Gbyte | |
Hardware configuration |
| |
Design of hardware configuration | Modular, up to 7 modules per CPU | |
Speed input |
| |
Number of speed inputs | 1 | |
Input voltage |
| |
● 24 V DC digital | Yes | |
Sensor input |
| |
Number of IEPE sensor inputs | 4 | |
Sampling frequency, max. | 46 875 Hz | |
Interfaces |
| |
Type of data transmission | Export of raw data as WAV file for further analysis (e.g. using CMS X-Tools) can be downloaded via browser/FTP, online data transfer to CMS X-Tools | |
Ethernet interface | Yes | |
Protocols |
| |
Bus communication | Yes | |
Web server |
| |
● HTTP | Yes | |
Interrupts/diagnostics/status information |
| |
Alarms |
| |
● Diagnostic alarm | Yes | |
Diagnostics indication LED |
| |
● for status of the inputs | Yes | |
● for maintenance | Yes | |
● Status indicator digital input (green) | No | |
Integrated Functions |
| |
Monitoring functions |
| |
● Monitoring of the sensor inputs | Yes; Cable break and short-circuit | |
● Vibration characteristic monitoring via RMS value of the vibration speed | Yes | |
● Vibration characteristic monitoring via RMS value of the vibration acceleration | Yes | |
● Vibration characteristic monitoring via diagnostic characteristic value | Yes | |
● Frequency-selective monitoring via vibration speed spectrum | Yes | |
● Frequency-selective monitoring via vibration acceleration spectrum | Yes | |
● Frequency-selective monitoring via envelope curve analysis | Yes | |
Measuring functions |
| |
● Physical measuring principle | Vibration acceleration | |
Measuring range |
| |
— Measurement range vibration frequency, min. | 0.1 Hz | |
— Measurement range vibration frequency, max. | 10 000 Hz | |
Standards, approvals, certificates |
| |
Certificate of suitability | CE | |
CE mark | Yes | |
China RoHS compliance | Yes | |
Ambient conditions |
| |
Free fall |
| |
● Fall height, max. | 0.3 m; five times, in product package | |
Ambient temperature during operation |
| |
● horizontal installation, min. | -20 °C | |
● horizontal installation, max. | 60 °C | |
● vertical installation, min. | -20 °C | |
● vertical installation, max. | 45 °C | |
Ambient temperature during storage/transportation |
| |
● Storage, min. | -40 °C | |
● Storage, max. | 70 °C | |
● Transportation, min. | -40 °C | |
● Transportation, max. | 70 °C | |
Air pressure acc. to IEC 60068-2-13 |
| |
● Operation, min. | 795 hPa | |
● Operation, max. | 1 080 hPa | |
● Storage/transport, min. | 660 hPa | |
● Storage/transport, max. | 1 080 hPa | |
Software |
| |
Browser software required | Web browser Mozilla Firefox (ESR31) or Microsoft Internet Explorer (10/11) | |
Connection method |
| |
required front connector | Yes | |
Design of electrical connection | Screw connection | |
Mechanics/material |
| |
Material of housing | Plastic: polycarbonate, abbreviation: PC- GF 10 FR | |
Dimensions |
| |
Width | 70 mm | |
Height | 112 mm | |
Depth | 75 mm | |
Weights |
| |
Weight, approx. | 260 g |