5
Siemens电缆代理商Siemens电缆代理商6ES73924BC500AA0连接电缆
浔之漫智控技术上海有限公司出售西门子S7-200PLC,西门子S7-400PLC,西门子S7-300PLC,LOGO!逻辑模块,西门子
ET200I/O模块,西门子S7-1200PLC,西门子电机,西门子低压电机,伺服电机,主轴电机,直线电机,扭矩电机,直流电机,
西门子工业以太网,西门子光钎电缆,工业交换机,通讯网卡,西门子网络通讯设备,网络模块,西门子总线电缆,紫色双芯电缆绿色4芯电缆,
蓝色双芯电缆,西门子总线接头,西门子驱动系统,伺服驱动,模块驱动,电源模块,西门子触摸屏,
精智TP2200触摸屏能通过MPI电缆和S7-200系列PLC通信么?如CPU224CN
我在TIA comfort V12里没找到S7-200的CPU啊。
佳答案
TIA comfort V12不支持S7-200,TP2200如果要和S7-200通讯必须走PROFIBUS,S7-200增么EM277模块。

程序已正常使用多年,出现问题后,上载来可以run。诊断如下:
Diagnostic buffer of module CPU 313C-2 DP
Order No./ Description Component Version
6ES7 313-6CF03-0AB0 Hardware 1
- - - Firmware V 2.0.12
Rack: 0
Slot: 2
Event 1 of 100: Event ID 16# 4562
STOP caused by programming error (OB not loaded or not possible, or no FRB)
Breakpoint in user program: Cyclic program (OB1)
Priority class: 1
FC number: 1
Module address: 378
Previous operating mode: RUN
Requested operating mode: STOP (internal)
Internal error, Incoming event
11:15:45.070 PM 04/27/2000
Event 2 of 100: Event ID 16# 2521
BCD conversion error
Affected register: accumulator 1
Requested OB: Programming error OB (OB121)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
11:15:45.056 PM 04/27/2000
Event 3 of 100: Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
11:15:45.033 PM 04/27/2000
Event 4 of 100: Event ID 16# 1381
Request for manual warm restart
STOP due to: STOP caused by programming error (OB not loaded or not possible, or no FRB)
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Requested OB: Startup OB (OB100)
Priority class: 27
Incoming event
11:15:45.032 PM 04/27/2000
佳答案
1、诊断信息:
BCD conversion error
Affected register: accumulator 1
Requested OB: Programming error OB (OB121)
OB not found, or disabled, or cannot be started in the in the current operating mode
Internal error, Incoming event
STOP due to: STOP caused by programming error (OB not loaded or not possible, or no FRB)
从上述诊断信息可看出是由于编程错误引起的STOP ,具体是由BCD码转换的错误。如果忽略这种错误可添加OB121,只需添加不需编程。
2、关于OB组织块:
CPU程序块里面需要添加一些对应的OB组织块,只需添加不需编程,当发生相应故障是CPU只报警,不停机。如:
OB81 电源故障
OB82 诊断中断
OB83 插入/拔出模块中断
OB85 优先级错误
OB86 扩展机架,DP主站系统或者分布式I/O故障
OB87 通讯故障
OB121编程错误
OB122 I/O访问错误
6ES73924BC500AA0连接电缆西门子CPU模块代理商西门子CPU模块代理商西门子CPU模块代理商西门子CPU模块代理商西门子CPU模块代理商Siemens电缆代理商Siemens电缆代理商Siemens电缆代理商Siemens电缆代理商Siemens电缆代理商Siemens电缆代理商
| 6XV1840-2AH10 |
| 6ES7590-1AB60-0AA0 |
| 6EP1333-2BA20 |
| 6ES7193-6BP00-0BA0 |