dv/dt filters plus VPL |
JTA:TEF1203-0GB Mdexx 带 VPL 的 dU/dt 滤波器 用于 SINAMICS G120 电压峰值限制 690V <(><<)>= 18.5 kW 400V <(><<)>= 7.5 kW SINAMICS Pool 软件 V4.7 SP10 或高版本 ,这是必需的 针对 G120 应用 SINAMICS Pool 软件 V5.1 SP1 或高版本 ,这是必需的 针对 S120 应用 |
dv/dt filter plus VPL
dv/dt filters plus VPL (Voltage Peak Limiter) limit the voltage rate-of-rise dv/dt to values < 500 V/μs and the typical voltage peaks to the following values according to the limit value curve to IEC/TS 60034‑17: 2006:
< 1350 V phase/phase at the motor terminals with a nominal DC link voltage of 935 V
< 1100 V phase/ground at the motor terminals with a nominal DC link voltage of 935 V
Standard motors with standard insulation and without insulated bearings can be used for converter operation if a dv/dt filter plus VPL is used.
JTA dv/dt filters can be operated with SINAMICS G120 firmware V4.7 SP10 or higher.
In terms of function, the dv/dt filter plus VPL consists of two components:
dv/dt reactor
Voltage limiting network, which cuts off the voltage peaks and feeds the energy back into the DC link.
| Frame size | ||||||
---|---|---|---|---|---|---|---|
| FSA | FSB | FSC | FSD | FSE | FSF | FSG |
PM240‑2 Power Module with integrated braking chopper | |||||||
200 V versions | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | – |
400 V versions | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
690 V versions | – | – | – | ✓ | ✓ | ✓ | ✓ |
Load-side power components | |||||||
dv/dt filters plus VPL 1) (for 400 V and 690 V versions only) | – | – | – | S | S | S | S |
S = Lateral mounting
– = Not possible
1) The 690 V versions of the PM240‑2 Power Modules require motors with a suitable isolating system for 690 V converter operation (IVIC‑C premium). The VSD10 line with corresponding SIMOTICS GP 1LE109 General Purpose motors or SIMOTICS SD 1LE159 Severe Duty motors is ideally suited for converter operation at 690 V.
Additional information is available in Catalog D 81.1.
Line voltage 380 ... 480 V 3 AC or 500 ... 690 V 3 AC | dv/dt filters plus VPL | |||
---|---|---|---|---|
| JTA:TEF1203-0GB | JTA:TEF1203-0HB | JTA:TEF1203-0JB | |
Rated current | A | 24 | 44 | 64 |
I th max | A | 38 | 70 | 104 |
Power loss at 150 Hz 690 V | kW | 0.125 | 0.303 | 0.404 |
Power connection input and output side |
| Screw terminals | Screw terminals | Screw terminals |
Conductor cross-section, max. | mm2 | 16 | 35 | 50 |
DC link connection 1) DCPS, DCNS |
| Screw terminals | Screw terminals | Screw terminals |
Conductor cross-section, max. | mm2 | 16 | 16 | 16 |
PE connection |
| Screw terminals | Screw terminals | Screw terminals |
Conductor cross-section, max. | mm2 | 16 | 35 | 50 |
Motor cable length, max. |
|
|
|
|
Shielded | m (ft) | 350 (1148) | 350 (1148) | 350 (1148) |
Unshielded | m (ft) | 525 (1723) | 525 (1723) | 525 (1723) |
Cable length, max. between the dv/dt filter plus VPL and the Power Module | m (ft) | 5 (16.4) | 5 (16.4) | 5 (16.4) |
Ambient temperature | °C (°F) | -20 ... +40 (-4 ... +104) 40 ... 50 (104 ... 122) with current derating 1.5 % per 1 K | -20 ... +40 (-4 ... +104) 40 ... 50 (104 ... 122) with current derating 1.5 % per 1 K | -20 ... +40 (-4 ... +104) 40 ... 50 (104 ... 122) with current derating 1.5 % per 1 K |
Degree of protection |
| IP00 | IP00 | IP00 |
Dimensions |
|
|
|
|
Width | mm (in) | 264 (10.39) | 264 (10.39) | 310 (12.20) |
Height | mm (in) | 260 (10.24) | 275 (10.83) | 375 (14.76) |
Depth | mm (in) | 220 (8.66) | 245 (9.65) | 280 (11.02) |
Weight, approx. | kg (lb) | 20 (44.1) | 29 (63.9) | 46 (101) |
Conformity |
| CE, UKCA | CE, UKCA | CE, UKCA |
Certificates of suitability |
| cURus, EAC | cURus, EAC | cURus, EAC |
Suitable for | Type | – | 6SL3210-1PE23-8 . L0 | 6SL3210-1PE24-5 . L0 |
Suitable for | Type | – | – | – |
Suitable for | Type | 6SL3210-1PH21-4 . L0 | 6SL3210-1PH22-7 . L0 | 6SL3210-1PH25-2 . L0 |
1) Short-circuit-proof cables are required.
Line voltage 380 ... 480 V 3 AC or 500 ... 690 V 3 AC | dv/dt filters plus VPL | |||
---|---|---|---|---|
| JTA:TEF1203-0KB | JTA:TEF1203-0LB | JTA:TEF1203-0MB | |
Rated current | A | 103 | 146 | 260 |
I th max | A | 160 | 230 | 416 |
Power loss at 150 Hz 690 V | kW | 0.415 | 0.520 | 0.857 |
Power connection input and output side |
| Flat connector for M8 cable lug | Flat connector for M10 cable lug | Flat connector for M10 cable lug |
Conductor cross-section, max. | mm2 | 95 | 120 | 2 × 120 or 1 × 185 |
DC link connection 1) DCPS, DCNS |
| M8 cable lug | M8 cable lug | M8 cable lug |
Conductor cross-section, max. | mm2 | 25 | 25 | 50 |
PE connection |
| M6 screw studs | M6 screw studs | M6 screw studs |
Conductor cross-section, max. | mm2 | 50 | 70 | 95 |
Motor cable length, max. |
|
|
|
|
Shielded | m (ft) | 450/525 (1476/1723) 2) | 450/525 (1476/1723) 2) | 450/525 (1476/1723) 2) |
Unshielded | m (ft) | 650/800 (2133/2625) 2) | 650/800 (2133/2625) 2) | 650/800 (2133/2625) 2) |
Cable length, max. between the dv/dt filter plus VPL and the Power Module | m (ft) | 5 (16.4) | 5 (16.4) | 5 (16.4) |
Ambient temperature | °C (°F) | -20 ... +40 (-4 ... +104) 40 ... 50 (104 ... 122) with current derating 1.5 % per 1 K | -20 ... +40 (-4 ... +104) 40 ... 50 (104 ... 122) with current derating 1.5 % per 1 K | -20 ... +40 (-4 ... +104) 40 ... 50 (104 ... 122) with current derating 1.5 % per 1 K |
Degree of protection |
| IP00 | IP00 | IP00 |
Dimensions |
|
|
|
|
Width | mm (in) | 400 (15.75) | 400 (15.75) | 460 (18.11) |
Height | mm (in) | 325 (12.80) | 360 (14.17) | 435 (17.13) |
Depth | mm (in) | 355 (13.98) | 380 (14.96) | 445 (17.52) |
Weight, approx. | kg (lb) | 77 (170) | 97 (214) | 172 (379) |
Conformity |
| CE, UKCA | CE, UKCA | CE, UKCA |
Certificates of suitability |
| cURus, EAC | cURus, EAC | cURus, EAC |
Suitable for | Type | 6SL3210-1PE27-5 . L0 6SL3210-1PE28-8 . L0 | 6SL3210-1PE31-1 . L0 6SL3210-1PE31-5 . L0 | 6SL3210-1PE31-8 . L0 |
Suitable for | Type | 6SL3211-1PE27-5 . L0 | 6SL3211-1PE31-1 . L0 | 6SL3211-1PE32-5 . L0 |
Suitable for | Type | 6SL3210-1PH28-0 . L0 | 6SL3210-1PH31-2 . L0 | 6SL3210-1PH31-7CL0 |
1) Short-circuit-proof cables are required.
2) Maximum overvoltage at the motor terminals <1350 V with cable lengths up to 450 m (1476 ft) shielded or 650 m (2133 ft) unshielded – maximum overvoltage at the motor terminals <1500 V with cable lengths up to 525 m (1723 ft) shielded or 800 m (2625 ft) unshielded.